Load Bank Testing

Test generator set with load banks, record and report generator performance & more.

IMG_3030.jpg
Load Bank Testing

● Provide resistive load bank testing under the specifications below for a two-hour period annually
● Record and report generator performance including time, voltage, current, frequency, power factor, water temperature, oil pressure, ambient air temperature, and other factors as deemed necessary as part of the overall load test.
● Not less than 75% of the nameplate rating for a total of two or four continuous hours. Or if otherwise specified differently.
● Engine inspections shall be conducted prior to the start of testing and readings shall be logged inno less than 15-minute increments